A0011036 August 2014 Rev. 22 Pollution Control Unit Installation, Operation, and Maintenance Manual Pollution Control Unit Save th
10Advanced Filter Pressure Monitoring Option The PCU Filter Monitoring Module (PCUFMM) utilizes proprietary algorithms to make determinat
11 The HMI for the PCU filter pressure monitor is a “Smart” rocker switch installed with a b
12 • Config PCU is configured at the factory. PCU has to be re-configured ONLY if filter types in any filter module are changed. To Configur
13Copper Wire Ampacity Wire Size AWG Maximum Amps 14 15 12 20 10 30 8 50 6 65 4 85 PCUFMM Wiring Before connecting power to the contro
14Troubleshooting The following table lists causes and corrective actions for possible faults shown on the HMI with the Pollution Co
15Fire System Pollution Control Units often require a fire system to be installed with the PCU. CORE or Ansul R-102 Fire Suppression Sy
16 Utility Cabinet Pollution Control Unit with Climate Controlled Utility Cabinet Installed
17 OPERATION Prior to starting up or operating the PCU, check all fasteners for tightness. In particular, check the module connection seal and the d
18Troubleshooting The following table lists causes and corrective actions for possible problems with the pollution control units and t
19MAINTENANCE To guarantee trouble free operation of this PCU, the manufacturer suggests following these guidelines. Most problems associate
2
20WARNING: FILTER PART NUMBERS OUTLINED BELOW ARE LISTED FOR USE IN THE PCU. USING ANY OTHER FILTERS WILL VOID WARRANTY AND AFFECT PERFORMANCE Stand
21450° F Gasket between Modules and doors 1500° F Gasket for Internal Joints
A0011036 August 2014 Rev. 22 Start-Up and Maintenance Documentation START-UP AND MEASUREMENTS SHOULD BE PERFORMED AFTER THE SYSTEM HAS BEEN AIR BALA
3TABLE OF CONTENTS WARRANTY ...
4WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months
5LISTINGS This pollution control unit (PCU) is ETL listed to standard UL-710, CAN/ULC-S646, CAN/ULC-S647 when installed in accordance with these
6INSTALLATION It is imperative that this unit is installed and operated with the designed airflow, filters, exhaust fan placement, a
7Recommended MIN Ductwork Sizes PCU Size Duct Height Duct Width PCU-1 23 in. 23 in. PCU-2 30 in. 30 in. PCU-3 35 in. 35 in. PCU-4 43 in. 4
8Equipment Rails The unit should be installed on a curb and/or rail elevated not less than 14” above any roof surface. Secure PCU
9Air Pressure Switch Option Switches are preset from plant to .15” w.c. above the internal static pressure of the PCU with clean filters. Air pressu